The following table shows noise reduction levels (in dB) recorded during testing:

Frequency (Hz) Noise reduction (dB)
  Type 7010 Type 7020
63 8.5 9.5
125 11.5 11.5
250 10 16.5
500 14.5 21.5
1000 21 39
2000 23.5 35.5
4000 24 38

NOTE:
Tests were carried out in accordance with ASTM E336-67T, Section A2.3 “Test procedure for measuring transmission loss in non-laboratory type configuration”. Field transmission loss was determined as specified in Section A2.3 E.336, defined as FTL = NR - 6.

No. of Intermediate Blades Standard Height (mm)
  Type 7010 & Type 7020
*2 590
3 740
4 890
5 1040
6 1190
7 1340
8 1490
9 1640
10 1790
11 1940
12 2090
13 2240
14 2390
15 2540

* Denotes minimum dimensional limitation.
NOTE:
Standard heights shown give maximum free inlet area; however, louvres can be manufactured to suit any opening dimensions.

Series 7000 – Type 7030

The Robertson Acoustic Louvre Type 7030 is a factory or site assembled, medium to high performance half-chevron louvre.

Series 7000 – Type 7040

The Robertson Acoustic Louvre Type 7040 is a factory or site assembled, high performance half chevron louvre.

The following table shows noise reduction levels (in dB) recorded during testing:

Frequency (Hz) Noise reduction (dB)
  Type 7030 Type 7040
63 8 12.5
125 15.5 24
250 18 24
500 26 31.5
1000 35.5 36.5
2000 37 39.5
4000 33 34

NOTE:
Tests were carried out in accordance with ASTM E336-67T, Section A2.3 “Test procedure for measuring transmission loss in non-laboratory type configuration”. Field transmission loss was determined as specified in Section A2.3 E.336, defined as FTL = NR - 6.

No. of Intermediate Blades Standard Height (mm)
  Type 7030 Type 7040
*2 1730 1172
3 2030 1507
4 2330 1846
5 2630 2183
6 2930 2520
7 3230 2857

* Denotes minimum dimensional limitation.
NOTE:
Standard heights shown give maximum free inlet area; however, louvres can be manufactured to suit any opening dimensions.