Acoustic Louvres
Series 7000 – Type 7010
The Robertson Acoustic Louvre Type 7010 is a
factory assembled, medium performance, halfchevron
louvre.
Series 7000 – Type 7020
The Robertson Acoustic Louvre Type 7020 is a
factory assembled, medium performance, full
chevron louvre.
The following table shows noise reduction levels
(in dB) recorded during testing:
| Frequency (Hz) |
Noise reduction (dB) |
| |
Type 7010 |
Type 7020 |
| 63 |
8.5 |
9.5 |
| 125 |
11.5 |
11.5 |
| 250 |
10 |
16.5 |
| 500 |
14.5 |
21.5 |
| 1000 |
21 |
39 |
| 2000 |
23.5 |
35.5 |
| 4000 |
24 |
38 |
NOTE:
Tests were carried out in accordance with ASTM E336-67T, Section A2.3
“Test procedure for measuring transmission loss in non-laboratory type
configuration”. Field transmission loss was determined as specified in
Section A2.3 E.336, defined as FTL = NR - 6.
| No. of Intermediate Blades |
Standard Height (mm) |
| |
Type 7010 & Type 7020 |
| *2 |
590 |
| 3 |
740 |
| 4 |
890 |
| 5 |
1040 |
| 6 |
1190 |
| 7 |
1340 |
| 8 |
1490 |
| 9 |
1640 |
| 10 |
1790 |
| 11 |
1940 |
| 12 |
2090 |
| 13 |
2240 |
| 14 |
2390 |
| 15 |
2540 |
* Denotes minimum dimensional limitation.
NOTE:
Standard heights shown give maximum free inlet area; however, louvres
can be manufactured to suit any opening dimensions.
Series 7000 – Type 7030
The Robertson Acoustic Louvre Type 7030 is
a factory or site assembled, medium to high
performance half-chevron louvre.
Series 7000 – Type 7040
The Robertson Acoustic Louvre Type 7040 is a
factory or site assembled, high performance half
chevron louvre.
The following table shows noise reduction levels (in
dB) recorded during testing:
| Frequency (Hz) |
Noise reduction (dB) |
| |
Type 7030 |
Type 7040 |
| 63 |
8 |
12.5 |
| 125 |
15.5 |
24 |
| 250 |
18 |
24 |
| 500 |
26 |
31.5 |
| 1000 |
35.5 |
36.5 |
| 2000 |
37 |
39.5 |
| 4000 |
33 |
34 |
NOTE:
Tests were carried out in accordance with ASTM E336-67T, Section A2.3
“Test procedure for measuring transmission loss in non-laboratory type
configuration”. Field transmission loss was determined as specified in
Section A2.3 E.336, defined as FTL = NR - 6.
| No. of Intermediate Blades |
Standard Height (mm) |
| |
Type 7030 |
Type 7040 |
| *2 |
1730 |
1172 |
| 3 |
2030 |
1507 |
| 4 |
2330 |
1846 |
| 5 |
2630 |
2183 |
| 6 |
2930 |
2520 |
| 7 |
3230 |
2857 |
* Denotes minimum dimensional limitation.
NOTE:
Standard heights shown give maximum free inlet area; however,